wtabess – Sat 28 Nov 2026 (EAT), coverage 100%
Deye: PV 59.7 kWh, load 49.7 kWh, grid 0.0 kWh, grid off 24.0 h (0 times)
| Battery | Max SOC | Min SOC | Charge in | Discharge out | Capacity (14-day) | Efficiency (14-day) | DC efficiency (14-day) |
|---|---|---|---|---|---|---|---|
| Deye | 100% | 79% | 8.68 kWh | 8.12 kWh | 31.2 kWh | 70.8% | 95.8% |
| Battery 1 | 91% | 68% | 8.00 kWh | 8.30 kWh | 30.7 kWh | 94.3% | – |
| Battery 2 | 89% | 67% | 6.90 kWh | 7.40 kWh | 28.9 kWh | 97.7% | – |
rockbess – Sat 28 Nov 2026 (EAT), coverage 100%
Deye: PV 19.4 kWh, load 16.8 kWh, grid 0.0 kWh, grid off 24.0 h (0 times)
| Battery | Max SOC | Min SOC | Charge in | Discharge out | Capacity (14-day) | Efficiency (14-day) | DC efficiency (14-day) |
|---|---|---|---|---|---|---|---|
| Deye | 100% | 71% | 5.71 kWh | 5.07 kWh | 14.8 kWh | 65.5% | 88.7% |
| Battery 1 | 80% | 70% | 2.90 kWh | 2.80 kWh | 30.0 kWh | 91.9% | – |
| Battery 2 | 80% | 71% | 2.90 kWh | 2.90 kWh | 36.1 kWh | 91.6% | – |
mirembess – Sat 28 Nov 2026 (EAT), coverage 100%
Deye: PV 16.1 kWh, load 13.4 kWh, grid 0.0 kWh, grid off 24.0 h (0 times)
| Battery | Max SOC | Min SOC | Charge in | Discharge out | Capacity (14-day) | Efficiency (14-day) | DC efficiency (14-day) |
|---|---|---|---|---|---|---|---|
| Deye | 100% | 63% | 5.44 kWh | 5.03 kWh | 10.0 kWh | 60.5% | 90.0% |
| Battery 1 | 81% | 68% | 5.10 kWh | 4.00 kWh | 33.5 kWh | 87.1% | – |
bcfbess – Sat 28 Nov 2026 (GMT), coverage 100%
Powerwall: PV 0.0 kWh, load 161.7 kWh, grid 174.5 kWh, grid off 0.0 h (0 times)
Deye: PV 0.0 kWh, load 0.4 kWh, grid 16.0 kWh, grid off 0.0 h (0 times)
| Battery | Max SOC | Min SOC | Charge in | Discharge out | Capacity (14-day) | Efficiency (14-day) | DC efficiency (14-day) |
|---|---|---|---|---|---|---|---|
| Powerwall | 100% | 10% | 13.46 kWh | 11.56 kWh | 11.6 kWh | 86.8% | – |
| Deye | 100% | 10% | 14.22 kWh | 12.72 kWh | 14.3 kWh | 76.9% | 87.5% |
| Battery 1 | 90% | 5% | 32.00 kWh | 29.40 kWh | 34.4 kWh | 92.4% | – |
| Battery 2 | 91% | 5% | 27.90 kWh | 25.50 kWh | 30.3 kWh | 92.2% | – |
Polled every 5 minutes. Page reloads every 2 minutes. The 24 and 48 hour graphs are redrawn after each poll, and the 7 and 14 day graphs every 20 minutes; panel titles give the time drawn. Gaps are filled daily from the BESS log files, synced 06:05–07:05 UK time. Capacity is AC, the average of the charge side (Solax charge counter per SOC rise while charging) and discharge side (discharge counter per SOC fall while discharging). 14-day figures use the days of the last 14 with data (noted if fewer). Efficiency is AC to AC, adjusted for the change in stored energy. The Deye row is the Deye inverter's battery, from the battery energy the BESS integrates from the battery's BMS power (or, without it, from the Deye's own counters), leaving out, for capacity, time at 98% SOC or more and runs that moved its SOC less than 2%. Its capacity is DC, at the battery. Its efficiency is from the energy put into the battery, PV and AC, to the AC it gives back, each moment's inverter losses shared in proportion to the flows, comparable with the Solax batteries' AC to AC (a count of days after it means fewer days had these figures); its DC efficiency is the round trip at the battery itself.